Technical specifications
8.1 Technical specifications
PAC2200CLP
78
Equipment Manual, 06/2021, L1V30820585B-02
Measuring inputs
Measuring category
CAT III (acc. to IEC 61010-2-030)
Input resistance (L-N)
1
MΩ
Measuring inputs for current (5 A device)
Only for connection to AC power systems via external current transformers (5 A device)
Measuring inputs
Rated current In I
e
1 A / 5 A
Max. permissible continuous current
10 A
Current impulse overload capability
100 A for 1 s
Zero point suppression level
10 mA / 45 mA
Measuring range
1 ... 120%
Apparent power consumption
Measuring range 1 A / per phase
4 mVA
Measuring range 5 A / per phase
0.115 VA
Measuring inputs for current (65 A device)
For direct connection to the AC system.
Measuring inputs
Reference current Iref (acc. to EN 50470-1)
10 A
Max. input current Imax
65 A
Current impulse overload capability
1990 A for 10 ms
Measuring range
0.5 ... 65 A
Power supply (5 A and 65 A devices)
Power supply
Design of the power supply
Wide range AC power supply
(supply from measuring voltage L1, L2 or L3)
Operating range
100 V - 230 V +/- 20%
Power consumption
5 VA
Overvoltage category
OVC III
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......