Commissioning
6
6.1
Overview
Prerequisites
•
The device has been installed.
•
The device has been connected in accordance with the possible connection methods.
Steps for starting up the device
1.
Apply the measuring voltage
2.
Parameterize the device
3.
Check measured values
Note
Check the connections
Incorrect connection can result in malfunctions and failure of the device.
Before starting up the PAC2200CLP, check that all the connections have been made correctly.
Note
When performing an insulation test of the entire installation with AC or DC, the device should
be disconnected before starting the test.
6.2
Applying the measuring voltage
The device is supplied with power via the measuring voltage.
Please consult the technical data or the type plate for the type and level of the possible
supply voltage.
See chapter Connections (Page 41).
WARNING
Do not apply voltage in excess of the rated voltage limit
Can cause death, serious personal injury, or equipment damage.
The maximum voltage listed in the technical data and on the rating plate must not be
exceeded.