Appendix
A.1 Modbus TCP
PAC2200CLP
94
Equipment Manual, 06/2021, L1V30820585B-02
A.1.2
Modbus exception codes
Overview
Table A- 2
Modbus exception codes
Exception codes Name
Meaning
Remedy
01
Illegal Func-
tion
Illegal function:
•
The function code in the re-
quest is not a permissible action
for the slave.
•
The slave is in a status in which
it cannot process a request of
this type. This is the case, for
example, if it has not yet been
configured and is requested to
return register values.
Check which function
codes are supported.
02
Illegal Data
Address
Illegal data address
This address is not permissible for
the slave. This is the case, for ex-
ample, if the combination of start
offset and transfer length is invalid.
Check the offset and the
number of registers.
03
Illegal Data
Value
Illegal data value:
The request contains a data value
that is not permissible for the slave.
This indicates an error in the re-
maining structure of a complex
request, e.g. an incorrect data
length.
Check that the specified
offset and the specified
data length in the com-
mand are correct.
04
Slave Device
Failure
Error in processing the data:
An indefinite error occurred when
the slave attempted to execute the
requested action.
Check that the specified
offset and the specified
data length are correct.
F0
Write Protec-
tion ON
The action has been rejected be-
cause the write protection is set.
Deactivate write protec-
tion.
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......