Commissioning
6.3 Parameterizing the device
PAC2200CLP
64
Equipment Manual, 06/2021, L1V30820585B-02
"Basic settings" parameter
Not available for 65 A devices.
"Current input" parameter
The "Current input" parameter specifies the values for the current input.
When measuring via current transformer, the device must know the current conversion ratio.
For this purpose, the primary and secondary current must be specified in the fields "PRIMARY
CURRENT" and "SECONDARY CURRENT".
Selection
Range
Factory setting
PRIMARY CURRENT
Freely adjustable.
Range: 1 A ... 10000 A
50 A
SECONDARY CURRENT Range: 1 A, 5 A
5 A
DISPLAY RANGE
Freely adjustable.
Range: 1 A ... 10000 A
50 A
I(n) display
Display of current in neutral conductor (calculated)
No:
•
Neutral current is displayed in menu item 3.0
Yes:
•
Neutral current is not displayed
Yes
You can configure the resolution of the current display in the "DISPLAY RANGE" menu item.
The setting has no impact on the measurement accuracy of the device. The recommended
setting is the current that is usually flowing in the system. If the usual current is 50 A, set the
display range to 50 A. In this case, the current is displayed with one decimal place.
"Write protection" parameter
The "Write protection" parameter is described later in this chapter.
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......