PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
13
Description
2
2.1
Performance features
The PAC2200CLP is a power monitoring device for measuring the basic electrical variables in
low-voltage power distribution. All the measured variables are shown on the PAC2200CLP
display. The device is capable of single-phase, two-phase or three-phase measurement and
can be used in TN, TT and IT systems.
Please note that the MID approval and the national approval according to PTB A50.7 are valid
for use in single-phase and three-phase systems. Single-phase operation is only permitted on
L1.
The PAC2200CLP is installed on a standard mounting rail.
Several versions of the PAC2200CLP power monitoring device are available:
•
5 A device:
X / 1 A and x / 5 A current transformers can be used for current measuring.
•
65 A device:
No current transformers are required for current measuring. The device is connected
directly to the low-voltage network. Current of up to 65 A can be measured directly.
The PAC2200CLP power monitoring device features an integrated Ethernet interface.
Thanks to the wide measuring voltage range of the PAC2200CLP, it can be connected directly
in the low-voltage network up to a nominal line voltage UL-L of 400 V.
Measurement
•
Measurement of all relevant electrical variables in an AC system
•
Averaging of all measured values directly on the device in two stages, which are
independent of each other and freely configurable (aggregation)
•
4-quadrant measurement for import and export
Counters and average power demand values
•
Recording of active, reactive and apparent energy by means of several energy counters
•
Calculation and storage of the last demand period average value for active and reactive
power for simple software-driven generation of load profiles
•
Calculation of average values for active and reactive power of the last completed demand
period for import and export
•
Time stamp of the current demand period acc. to ISO8601 (local and UTC time)
•
MID-certified active energy counter for import and export (Measuring Instruments
Directive 2014/32/EU)
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......