Appendix
A.1 Modbus TCP
PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
123
Bytes in hex
Description
2D
Length of 2nd record in a row starting with OID 0x2CE3 in bytes (including this byte)
5E 84 D3 1C
00 00 0E 10
00 00 2C E3
41 90 D1 A5
00 00 00 00
41 41 B4 F4 51 81 7A 00
00 00 00 00 00 00 00 00
00 00 07 7E
00 01 00 40
0x2D data bytes of record 0x02 with OID 0x2CE3
timestamp act.period
Timezone offset in s
OID act. Period (unique period entry identification
index)
Active energy Import act. Period in Wh
Active energy Export act. Period in Wh
Active energy counter reading Import T1+T2 act.
Period in Wh
Active energy counter reading Export T1+T2 act.
Period in Wh
Real load profile period length act. Period in millisec-
onds
Information flag bytes act. period
unix time UTC
signed long
unsigned long
float
float
double
double
unsigned long
Bitfield
4 byte
4 byte
4 byte
4 byte
4 byte
8 byte
8 byte
4 byte
4 byte
Example of readout of the logbook (event memory), request frame
7 bytes
1 byte
1 byte
1 byte
5 bytes
MBAP Header
Function code 0x64
Data log identifier (event
memory)
Data identifier (all
events)
Advanced data identi-
fiers (4 byte OID and 1
byte number of rec-
ords.)
0x0000 0x0000
0x0009 0x01
0x64
0x01
0x00
0x00000000 0x04
Example of readout of the logbook (event memory), response frame
Bytes in hex
Description
00 00 00 00 00 EE 01
MBAP Header
64
Modbus user defined function code
EB
payload length in bytes (starting with the following byte to the end, excluding CRC)
01
Data log identifier -> event memory
00
Data identifier -> all events
0x00000000
Set the read pointer to first OID of the event memory
04
Number of records inserted in this telegram (may be smaller than requested)
39
Length of first record in bytes (including this byte)
62 7F 5B D7
00 00 0E 10
00 00 00 01
00 00 00 02
00 00 00 01
00 00 00 64
00 00 00 05
FF FF FF FF
41 47 E3 CC 9E 65 69 00
00 00 00 00 00 00 00 00
00 00 00 01
56 03 02 00
Date in UTC
Timezone offset in s
OID of Logbook record
Corresponding period OID
Type of record (1=current transformer settings change)
Primary transformer setting
Secondary transformer setting
Reserved
Energy counter value import (T1+T2) at logging time
Energy counter value export (T1+T2) at logging time
Logbook Version
Firmware version
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......