Description
2.4 Electronic trip unit ETU
Air circuit breaker 3WL10
66
Manual, 11/2017, L1V30499596002-01
2.4.5
Metering functions of the ETUs of the 6-series
The electronic trip units of the 6-series can be expanded with the metering functions
MF Basic or MF Advanced. These measure the voltage between the phases with internal
voltage tap - optionally on the incoming or outgoing feeder side - and can therefore calculate
and transmit values for power, energy, phase difference, etc., taking the current signals into
consideration.
●
MF Basic provides many measured values in accordance with IEC 61557-12
●
MF Advanced provides not only the measured values described but also many enhanced
protection functions, which are listed in Chapter Parameters of the trip units (Page 54).
Faults such as overvoltages in the power system can therefore be detected before the
contacts of the circuit breaker are closed. In this way, the ETU can also power the
metering module MF Advanced directly from the busbar itself if no auxiliary power supply
is provided via the Breaker Connect module.
Metering functions of the ETUs of the 6-series
Instantaneous values
Measured values Precision
Reference standard: IEC 61557-12
Metering module
MF required
Currents (rms value)
A
L1, L2, L3, N
1 %, class 1
—
Ground fault current
A
I
g
2 %
—
Phase-to-phase voltage (rms value) V
U12, U23, U31
0.5 %
●
Phase-to-neutral voltage (rms value) V
U1, U2, U3
0.5 %
●
Phase sequence
—
—
●
Frequency
Hz
f
0.2 %
●
Active power
kW
P1, P2, P3, P
tot
2 %
●
Reactive power
kvar
Q1, Q2, Q3, Q
tot
2 %
●
Apparent power
kVA
S1, S2, S3, S
tot
2 %
●
Power factor (p.f.)
L1, L2, L3, N
2 %
●
Peak factor
total
—
●
Counter
(recorded since installation or last reset)
Measured values Precision
Metering module
MF required
Active energy
kWh
E
p
total
E
p
drawn
E
p
consumed
2 %
●
Reactive energy
kvarh E
q
total
E
q
drawn
E
q
consumed
2 %
●
Apparent energy
kVAh E
s
total
2 %
●
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......