Accessories
3.2 Electronic accessories
Air circuit breaker 3WL10
82
Manual, 11/2017, L1V30499596002-01
Ready-to-close signaling switch (RTC)
The signaling contact for ready-to-close (RTC) is used to query whether the circuit breaker is
ready for closing.
The following conditions must be met before the circuit breaker is ready to close:
●
Circuit breaker in the OPEN position
●
Springs charged
●
Switch-off command or interlocking with switch-off command is not pending
●
Circuit breaker reset due to tripping of the electronic trip unit ETU
Standard contact
Contact for digital signal
Type
Changeover contact
Smallest load
100 mA at 24 V
1 mA at 5 V
Breaking capacity
DC
24 V
—
0.1 A
250 V
0.5 A at 0 ms
—
0.2 A at 10 ms
—
AC
250 V
3 A at cosφ 0.7
—