background image

Ulusoy URING12-24 - LL

C

- SF 

6

 Insulated

 

Compact RMU Switchgear with 

Vacuum Circuit Breaker

 

User Manual 

12-24kV / 200-630A / 21kA-3s

www.

eaton

.com

Summary of Contents for Ulusoy URING12-24-LLC-SF6

Page 1: ...Ulusoy URING12 24 LLC SF6 Insulated Compact RMU Switchgear with Vacuum Circuit Breaker User Manual 12 24kV 200 630A 21kA 3s www eaton com...

Page 2: ...IT BREAKER UNIT 8 2 1 CLOSING THE SWITCHGEAR DOOR 8 2 2 OPENING THE EARTHING SWITCH 8 2 3 CHARGING AND CLOSING THE DISCONNECTOR 8 2 4 CHARGING AND CLOSING THE CIRCUIT BREAKER 8 3 CUTTING CIRCUIT BREAK...

Page 3: ...sibility of the manufacturer More specifically The equipment must be handled and transported appropriately from the factory to the place of installation All intermediate storage should occur in condit...

Page 4: ...ust be isolated from the supply voltage Warning Risk of injury from movable parts in mechanical drives Before performing maintenance work Isolate the system from the supply voltage Release the circuit...

Page 5: ...tly on the ground or on a pallet depending on the type of handling involved To handle assemblies of up to 5 functional units one of the following methods must be used Using a forklift truck or pallet...

Page 6: ...ed underneath the switchgear Another option is to slide the cubicles over rods these same rods can be used to help get over the cable pit To handle 5 functional unit assemblies consisting of either co...

Page 7: ...contamination from dust smoke corrosive and or inflammable gases vapours or salt The switchgear must be protected from the rain and the humidity conditions should be as follows o the mean relative hum...

Page 8: ...g 12 24 LLF is 3 way unit in a single SF6 tank Two incoming outgoing unit with load break switch and one transformer protection unit with fuse combination This is 3 way design Uring 12 24 RMU can be d...

Page 9: ...Remote Controller Button optional Operating Handle 6 ACCESSORIES Cable Bushings Interface C Cable Clamps Earth Bar...

Page 10: ...URING 12 24 LLC SF6 INSULATED COMPACT RMU SWITCHGEAR WITH VACUUM CIRCUIT BREAKER 7 DIMENSIONS...

Page 11: ...cannot be delivered with cells In Output Cells To check cable faults Turn the breaker on Turn the disconnector on Turn the earthing disconnector off Open the cell front cover Place the cable test devi...

Page 12: ...GEAR DOOR Earthing switch must be closed for closing opening the switchgear door In the first step the door is open load break switch is open and the earthing switch is closed Put the bottom side of t...

Page 13: ...H Put the lever into the earthing switch lever hole Remove the handle from earthing switch lever hole Check the position of the earthing switch It must be in open position now Rotate the lever in the...

Page 14: ...ng charge lever hole and rotate in the direction of arrow Clockwise Push the closing I button to close load break switch If there is DC on the auxilliary contacts turn the manuel motor switch button t...

Page 15: ...ch must be closed for closing opening the switchgear door In the first step the door is open disconnector switch is open and the earthing switch is closed Put the bottom side of the door to the switch...

Page 16: ...BREAKER 8 2 2 OPENING THE EARTHING SWITCH Put the lever into the earthing switch lever hole Remove the handle from earthing switch lever hole Check the position of the earthing switch It must be in op...

Page 17: ...rrow Clockwise If there is DC on the auxiliary contacts turn the manual motor switch button to the motor selection Then the spring will be automatically charged by the motor Push the closing I button...

Page 18: ...otate in the direction of arrow Clockwise If there is DC on the auxiliary contacts turn the manual motor switch button to the motor selection Then the spring will be automatically charged by the motor...

Page 19: ...pening O button to close load break switch Put the key removed from the circuit breaker to disconnector safety lock Push the opening O button to close load break switch Check the position indicator fo...

Page 20: ...EAKER 8 3 3 CLOSING EARTHING SWITCH Put the lever into the earthing switch lever hole Remove the handle from earthing switch lever hole Check the position of the earthing switch It must be in close po...

Page 21: ...8 3 4 OPENING THE SWITCHGEAR DOOR Push the door upwards Pull the door towards yourself The door is opened...

Page 22: ...CLOSING EARTHING SWITCH Push the opening O button to open load break switch Put the lever into the earthing switch lever hole Check the position indicator for open position Rotate the lever in the dir...

Page 23: ...8 4 3 OPENING THE SWITCHGEAR DOOR Push the door upwards Pull the door The door is opened...

Page 24: ...URING 12 24 LLC SF6 INSULATED COMPACT RMU SWITCHGEAR WITH VACUUM CIRCUIT BREAKER 9 CABLE CONNECTION 10 OVER PRESSURE FLAP POSITION T connector interface C for incoming outcoming connection...

Page 25: ...11 COMBINING MODULAR CUBICLES Modular Cubicles are combined by using 6 pieces of M8x30 bolt Prior to assembly silicon crossing bushings and contact holes must be cleaned well...

Page 26: ...n is to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our customers effectively manage electr...