8.2.3 CHARGING AND CLOSING THE DISCONNECTOR
Insert the lever into spring charge lever
hole and rotate in the direction of arrow.
(Clockwise)
If there is DC on the auxiliary contacts, turn
the manual-motor switch button to the
motor selection. Then the spring will be
automatically charged by the motor.
Push the closing (I) button to close load break switch.
Check the position indicator for close position and
remove the key from disconnector safety lock.