4.2 Power supply, grounding, and connection
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
119
4.2.1
Isolating distances and insulating equipment
When live parts are installed, the following rules must be followed:
●
Minimum isolating distance between the phases:
Rated insulation voltage U
i
Smallest distance
1000 V
acc. to IEC 61439: 14 mm
Siemens recommendation: 25 mm
●
Isolating distances within the switchboard panel
To observe the isolating distances inside the panel, the following minimum dimensions for
the interior of the panel must be observed:
A
3-pole
W
4-pole
C
D
Fixed break-
er
250 mm 322 mm
≤ 440 V: 332.5 mm
> 440 V: 382.5 mm
130 mm
Withdrawable
breaker
280 mm 350 mm
≤ 440 V: 390 mm
> 440 V: 440 mm
252 mm