Application planning
4.2 Power supply, grounding, and connection
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
121
4.2.2
Power loss
To ensure the electrical switchboards have the capacity to carry rated uninterrupted current,
the power loss of the circuit breaker must be considered in planning the electrical
switchboard.
The values shown in the table refer to the total power for three and four-pole circuit breakers
with balanced loads at a current that correspond to the rated uninterrupted current I
u
at
50/60Hz.
Power loss
I
u
630 A
800 A
1000 A
1250 A
Fixed breaker
[W]
31
50
78
122
Withdrawable breaker
[W]
62
100
156
244
The power losses have been calculated according to IEC 60947.