Operation
6.2 Alarms
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
163
L
S
I
G
Alarm / status
Measure / comment
On
On
Tripping on hardware
fault
Check the circuit
breaker and
accessories.
Flashing fast
(2 Hz)
Flashing fast
(2 Hz)
Temperature alarm
Lower the ambient
temperature or
reduce the continuous
operating current.
On
Pre-alarm L, power
flow is greater than
90 % of the threshold
value
On
Circuit breaker has
been tripped by the
L release
Clear faults in the
power system and
close the circuit
breaker again.
On
Circuit breaker has
been tripped by the
S release
Clear faults in the
power system and
close the circuit
breaker again.
On
Circuit breaker has
been tripped by the
I release
Clear faults in the
power system and
close the circuit
breaker again.
On
Circuit breaker has
been tripped by the
G release
Clear faults in the
power system and
close the circuit
breaker again.
Flashing fast
(2 Hz)
Threshold has been
exceeded, tripping
delay is elapsing
Reduce rated current
(disconnect loads)
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......