Description
2.4 Electronic trip unit ETU
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
63
Alarms and functions
ETU650 LSI
ETU660 LSIG
Alarms
Pre-alarms PAL response thresholds - function trigger
Enabling/disabling of PAL response threshold
overload current I
r pal(1)
●
●
Enabling/disabling of PAL response threshold
overload current I
r pal(2)
●
●
Setting range for PAL response threshold
overload current I
r pal(1)
= I
r
x …
50 %, 100 % (in steps of 1 %)
Default value: 50 %
50 %, 100 % (in steps of 1 %)
Default value: 50 %
Setting range for PAL response threshold
overload current I
r pal(2)
= I
r
x …
50 %, 100 % (in steps of 1 %)
Default value: 50 %
50 %, 100 % (in steps of 1 %)
Default value: 50 %
Enabling/disabling of PAL response threshold
rated current I
n pal(1)
●
●
Enabling/disabling of PAL response threshold
rated current I
n pal(2)
●
●
Setting range for PAL response threshold
rated current I
n pal(1)
= I
n
x …
0.1 to 10 (in steps of 0.01)
Default value: 3
0.1 to 10 (in steps of 0.01)
Default value: 3
Setting range for PAL response threshold
overload current I
n pal(2)
= I
n
x …
0.1 to 10 (in steps of 0.01)
Default value: 3
0.1 to 10 (in steps of 0.01)
Default value: 3
Crossing the response threshold rated
current I
n pal(1)
Direction: from bottom,
or from top
Default value: bottom → top
Default value: bottom → top
Crossing the response threshold rated
current I
n pal(2)
Direction: from bottom,
or from top
Default value: bottom → top
Default value: bottom → top
Checking the phase sequence / alarm
1)
●
●
Checking the phase sequence can be enabled/
disabled
●
●
Setting range for phase sequence
L1L2L3; L3L2L1
Default value: L1L2L3
L1L2L3; L3L2L1
Default value: L1L2L3
Trip/alarm COS PHI
1)
●
●
Trip COS PHI can be enabled/disabled
●
●
Setting range for checking the COS PHI
0.50 to 0.95 (in steps of 0.01)
Default value: 0.95
0.50 to 0.95 (in steps of 0.01)
Default value: 0.95
Functions Frequency adaptation
●
●
Frequency adaptation for ETUs of the 3-series
with DIP switch, for ETUs of the 6-series with
menu
50Hz; 60Hz
Default value: 50Hz
50Hz; 60Hz
Default value: 50Hz
Nominal voltage adaptation
●
●
Nominal voltage
100 V AC to 690 V AC
Default value: 400 V AC
100 V AC to 690 V AC
Default value: 400 V AC
1)
Only available with MF Basic or MF Advanced metering function
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......