Accessories
3.2 Electronic accessories
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
81
Position signaling switch PSS for guide frame
The position auxiliary contacts are used in the withdrawable breaker and signal whether the
circuit breaker is in the racking position DISCONNECT, Test, or CONNECT.
Breaker position
Auxiliary contacts
Main circuit connection
CONNECT: Inserted
Connected
Connected
TEST: Test position
Connected
Isolated
DISCON (DISCONNECT): Removed
Disconnected
Isolated
The position signaling switches are always installed in the guide frame. However, the user
can modify 24 V digital signals in the device configuration to meet the requirements for small
loads, e.g. for PLC connection.
Configuration
Position auxiliary contacts - PSS
6 auxiliary contacts
Standard contact 400 V
•
Contact for digital signal 24 V
•
Standard contact
Contact for digital signal
Type
Changeover contact
Changeover contact
Smallest load
100 mA at 24 V
1 mA at 5 V
Breaking capacity
DC
24 V
—
0.1 A
125 V
0.3 A at 0 ms
—
250 V
0.15 A at 0 ms
—
AC
250 V
5 A at cosφ 1
—
5 A at cosφ 0.7
—
5 A at cosφ 0.3
—
400 V
3 A at cosφ 1
—
2 A at cosφ 0.7
—
1 A at cosφ 0.3
—
Signaling diagram of the position signaling switch PSS:
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......