Instructions for  Digitrip RMS 

310 

Trip Unit For Use with 

R-Frame Breakers 

TABLE 

OF 

CONTENTS 

Description 

Page 

1.0 

General Information.. 

. . . . . . . . . . . . . . . . . . . . .  

1.1 

Protection.. 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

1.2 

Testing.. 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

2.0 

UL Listed Devices 

. . . . . . . . . . . . . . . . . . . . . . .  

3.0 

Principle of  Operation. 

. . . . . . . . . . . . . . . . . . . . .  

3.1 

General.. 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

3.2 

. . . . . . . . . . . . . . . . . . . . . . . . . . . .  

3.3 

Short 

Trip 

. . . . . . . . . . . . . .  

3.4 

Ground Fault Protection. 

. . . . . . . . . . . . . . . . . . .  

4.0 

Protection Settings 

. . . . . . . . . . . . . . . . . . . . . . .  

4.1 

General 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

4.2 

Short Delay Pick-up Settings 

. . . . . . . . . . . . . . . .  

4.3 

Short Delay Time Settings 

. . . . . . . . . . . . . . . . . .  

4.4 

Instantaneous Pick-up 

. . . . . . . . . . . . . . . . . . . . .  

4.5 

Ground Fault Pick-up Setting 

. . . . . . . . . . . . . . .  

4.6 

Ground Fault Time Setting 

. . . . . . . . . . . . . . . . .  

6.0 

Frame Ratings and Ratings Plugs 

. . . . . . . . . . . .  

7.0 

Reference.. 

. . . . . . . . . . . . . . . . . . . . . . . . . . . .  

7.1 

Digitrip RMS Trip Assemblies. 

. . . . . . . . . . . . . . .  

7.2 R-Frame Molded Case Circuit 

Breakers 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

5.0 

Testing 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

WARNING 

DO NOT 

TO INSTALL 

OR 

PERFORM MAIN- 

TENANCE ON EQUIPMENT WHILE IT 

IS 

ENERGIZED. 

DEATH, SEVERE PERSONAL INJURY, 

OR 

SUBSTAN- 

TIAL PROPERTY DAMAGE CAN RESULT FROM CON- 
TACT WITH  ENERGIZED EQUIPMENT. ALWAYS 
VERIFY THAT NO VOLTAGE 

IS 

PRESENT BEFORE 

PROCEEDING WITH THE TASK, AND ALWAYS FOL- 
LOW GENERALLY ACCEPTED SAFETY PROCE- 
DURES. 

THE CUTLER-HAMMER 

IS NOT LIABLE 

OF ITS PRODUCTS. 

The user is cautioned to observe all recommendations, 
warnings, and cautions relating to the safety of personnel 
and equipment as well as all general and local health and 
safety laws, codes, and procedures. 

FOR THE MISAPPLICATION 

OR MISINSTALLATION 

The recommendations and information contained herein 
are based on Cutler-Hammer experience and judgement, 

but should not be considered to be 

or cover- 

ing every application or circumstance which may arise. If 

any questions arise, contact Cutler-Hammer for further 

information or instructions. 

GENERAL INFORMATION 

1.1 

Protection 

The Digitrip 

RMS 31 

0, 

illustrated in Figure 1, is an elec- 

tronic trip unit that incorporates a microprocessor-based 
custom application specific integrated circuit design for 

use with R-Frame Molded Case Circuit Breakers. 

Fig. 

Digitrip RMS 

310 

Unit for use with R-Frame 

Circuit Breakers 

The Digitrip 

RMS 310 provides true RMS current sensing 

for proper correlation with thermal characteristics of con- 
ductors and equipment. Interchangeable rating plugs are 

provided to establish the continuous current rating of 
each circuit breaker. 

Effective 

February 2006 Supersedes I.L. 29C883C dated July 2003

I.L. 29C883E

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...S PRODUCTS The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment as well as all general and local health and safety laws codes and...

Page 2: ...eratures above 40 C with circuit breaker currents near full load For ambient conditions above 40 C and where the maxi mum ampere rating plug has been installed derating of the circuit breaker frame sh...

Page 3: ...e available see Figure 2 2 The 1 setting gives a trip responsewith no intentional delay Instantaneous 4 4 Instantaneous Pickup Setting For catalog numbers RES16OOLSI RES2000LS1 RES2500LS1 RES1600LSIG...

Page 4: ...Settings A B C D E F H K Specific Amperes Given in Table 1 2 Fig 2 3 GroundFault Pick Up Settings Short Delay Time r lSec Available Settings I l 2 3Seconds with Flat Response I I Fig 2 2 Short Delay...

Page 5: ...of the trip unit is set 2 The short delay pick up setting is a multiple of I 3 The ground pick up setting is independent of I Rating Plugs for the Digitrip RMS 310 Trip Units are marked for and may b...

Page 6: ...iiomat Fig 3 2 Trip Unit Nameplate Catalog Nos RES1600LS1 RESZOOOLSI and RES2500LSI ilrp RMS 310 1 Gnd Fig 3 3 Trip Unit Nameplate Catalog Nos RES1600LSG RESZOOOLSG and RES2500LSG Fig 3 4 Trip Unit Na...

Page 7: ...ating Plug Setting Amperes See Fig 2 6 a n d Fig 2 7 for Continuation of Short Time and Instantaneous Portions of Curves Current I Fig 5 1 OptionalAdjustable Ampere Setting Rating Plug Used in the Dig...

Page 8: ...Time 0with Adjustable Short Delay Pick up or Short Delay Digitrip RMS 310 Trip Unit Type Catalog Numbers RES1600LS RESl6OOLSI RES16OOLSG RESl600LSIG RES2000LS RES2000LSI RES2000LSG RES2000LSIG RES2500...

Page 9: ...able Trip Unit Ampere Rating Adjustable Rating Plugs 1600A 800A 1OOOA 1200A 1600A In 800A 1OOOA 1250A 1600AO In 2000A 1OOOA 1200A 1600A 2000A In 1000A 1250A 1600A 2000AO In 1200A 1600A 2000A 2500A In...

Page 10: ...NOTES Effective February 2006 I L 29C883E Page 10 Courtesy of NationalSwitchgear com...

Page 11: ...I L 29C883E NOTES EffectiveFebruary 2006 Page 11 Courtesy of NationalSwitchgear com...

Page 12: ...6 Printed USA TQC All Rights Reserved 2001 Eaton Corporation www eatonelectrical com tel 1 899 525 2000 USA Moon Township PA 15108 4312 1000 Cherrington Parkway Eaton Electrical business unit Eaton Co...