background image

The Digitrip 

RMS 31 

Trip Unit is completely self-con- 

tained and when the circuit breaker is closed, requires no 
external control power to operate its protection systems. 

It operates from current signal levels and control power 

derived through current sensors integrally mounted in the 
ci rcu i t b rea ke 

r. 

Digitrip RMS 310 Trip  Units are suitable for 

Hz AC 

applications only. 

The Digitrip 

RMS 31 

Trip Unit is available in 4 different 

types. Each trip unit contains a fixed long delay time func- 
tion (adjusted by changing the rating plug), and may be 
equipped with a maximum of two phase and two ground 

(time-current) adjustments to meet specific application 
requirements. The types of  adjustments available for 

each model include the following, which are illustrated in 

Figures 3.1 through 3.4. 

Adjustment 

Refer to 
Figure 

1) 

Short Delay Pick-up 

3.1 

2) 

Short Delay (Inst.) 

3.2 

Delay 

Time 

3) 

Short Delay Pick-up/ 

3.3 

Ground Fault Pick-up/ 
Ground Fault Time 

4) 

Short Delay (Inst.) 

3.4 

Delay 

Fault 

Time 

1.2 Testing 

Test  points (Figs. 3.1 through 3.4) are provided for func- 
tional field testing of the trip unit when connected to a test 

kit (Catalog 

No. 

2.0 UL LISTED DEVICES 

The Digitrip 

RMS 31 

Trip Unit is listed in accordance 

with Underwriters Laboratories, Inc. Standard UL 489, 

under file 

and satisfies the applicable require- 

ments of the International Electrotechnical Commission 
(IEC) recommendations for  molded case circuit breakers. 

3.0 PRINCIPLE 

OF 

OPERATION 

In open air at 

an R-Frame circuit breaker with a 

Digitrip RMS 310 Trip  Unit installed will carry continu- 

ously up to  1600,2000, or 2500 amperes without 
exceeding a 50°C rise at the terminals. The calibration of 

the trip unit is insensitive to ambient temperatures over a 

range of 

-20” 

to 

However, the trip unit contains 

thermal temperature protective circuitry that initiates a 
trip operation for self-protection 

if the internal ambient 

temperature at the printed circuit board (PCB) reaches 
approximately 100°C. This may occur for open-air tem- 

peratures above 40°C with circuit breaker currents near 

full load. 

For ambient conditions above 40°C and where the maxi- 
mum ampere rating plug has been installed, derating of 

the circuit breaker frame should be considered to avoid 
exceeding a safe terminal temperature operating range. 

Consult Cutler-Hammer for  recommendations. 

3.1 

General 

The Digitrip 

RMS 31 

Trip Unit provides a tripping signal 

to the flux transfer shunt trip when current and time delay 
settings are exceeded. This is accomplished by employ- 

ing the Cutler-Hammer custom designed integrated cir- 

cuit 

chip, which includes a microcomputer to 

perform its numeric and logic functions. 

In the Digitrip 

RMS 31 

Trip Unit, all required sensing and 

tripping power to operate its protection function is derived 
from the current sensors in the circuit breaker. The sec- 
ondary currents from these sensors provide the correct 

input information for the protection functions, as well as 

tripping power, whenever the circuit breaker is carrying 
current. These current signals develop voltages across 
the appropriate calibrating resistors. 

The microcomputer, in cyclic fashion,  repeatedly scans 
the voltage values across each calibrating resistor and 
enters these values into memory. These data are used to 
calculate true 

RMS current values, which are then 

repeatedly compared with the protection function settings 

and other operating data stored in memory. The software 
program then determines whether to initiate protection 
functions, including tripping the breaker through the flux 
transfer shunt trip device in the circuit breaker. 

A green status light indicates the operational status of 
the trip unit.  If the load current through the circuit break-

of a properly functioning trip unit.  If the status light is not
blinking, the current through the breaker may be less
than 20% of the maximum current rating of the trip unit

If the current exceeds 20% and the status light is not 

blinking, use the STK2 test kit to investigate.  IF THE  
STATUS LIGHT IS ON STEADY, IT INDICATES A 

Effective February 2006

I.L. 29C883E

Page 2 

TRIP IS PENDING.

er exceeds approximately 20% of the maximum current
rating of the tirp unit, the status light will blink on and off

once each second.  A blinking status light is an indication 

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...S PRODUCTS The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment as well as all general and local health and safety laws codes and...

Page 2: ...eratures above 40 C with circuit breaker currents near full load For ambient conditions above 40 C and where the maxi mum ampere rating plug has been installed derating of the circuit breaker frame sh...

Page 3: ...e available see Figure 2 2 The 1 setting gives a trip responsewith no intentional delay Instantaneous 4 4 Instantaneous Pickup Setting For catalog numbers RES16OOLSI RES2000LS1 RES2500LS1 RES1600LSIG...

Page 4: ...Settings A B C D E F H K Specific Amperes Given in Table 1 2 Fig 2 3 GroundFault Pick Up Settings Short Delay Time r lSec Available Settings I l 2 3Seconds with Flat Response I I Fig 2 2 Short Delay...

Page 5: ...of the trip unit is set 2 The short delay pick up setting is a multiple of I 3 The ground pick up setting is independent of I Rating Plugs for the Digitrip RMS 310 Trip Units are marked for and may b...

Page 6: ...iiomat Fig 3 2 Trip Unit Nameplate Catalog Nos RES1600LS1 RESZOOOLSI and RES2500LSI ilrp RMS 310 1 Gnd Fig 3 3 Trip Unit Nameplate Catalog Nos RES1600LSG RESZOOOLSG and RES2500LSG Fig 3 4 Trip Unit Na...

Page 7: ...ating Plug Setting Amperes See Fig 2 6 a n d Fig 2 7 for Continuation of Short Time and Instantaneous Portions of Curves Current I Fig 5 1 OptionalAdjustable Ampere Setting Rating Plug Used in the Dig...

Page 8: ...Time 0with Adjustable Short Delay Pick up or Short Delay Digitrip RMS 310 Trip Unit Type Catalog Numbers RES1600LS RESl6OOLSI RES16OOLSG RESl600LSIG RES2000LS RES2000LSI RES2000LSG RES2000LSIG RES2500...

Page 9: ...able Trip Unit Ampere Rating Adjustable Rating Plugs 1600A 800A 1OOOA 1200A 1600A In 800A 1OOOA 1250A 1600AO In 2000A 1OOOA 1200A 1600A 2000A In 1000A 1250A 1600A 2000AO In 1200A 1600A 2000A 2500A In...