background image

I.L. 29C883E

l²t ramp function for trip units with catalog number suf- 

fixes 

LS 

and 

LSG. 

A flat response time delay action is 

provided by trip units with catalog number suffixes 

LSI 

and LSIG  unless the instantaneous 

(I) setting is selected. 

3.4 Ground Fault Protection: 

When selected, ground 

fault pickup and time delay settings shown in Table 

1-2 

allow selective ground fault coordination with other circuit 
protection devices. 

An optional Automatic Trip Relay (ATR) may be furnished 
with the circuit breaker and is mounted underneath the 
trip unit as illustrated in Figure 

4. 

The ATR  provides a 

contact closure when a ground fault trip occurs. The con- 

nections required are shown in 

I.L. 

4.0 PROTECTION SETTINGS 

4.1 General 

Prior to placing any circuit breaker in operation, each trip 
unit protection setting must be set to the values specified 
by the engineer responsible for the installation. The avail- 

able settings along with the effect of  changing the set- 
tings are illustrated in Figures 

2.1 

to 

2.4. 

The installed rating plug establishes the maximum con- 
tinuous current rating 

(I,)  of  the circuit breaker. Short 

delay current settings are defined in multiples of 

I,. 

Over- 

ride is set at 

One to four time and pick-up adjustment settings are 
available depending on the particular trip unit purchased. 
An eight position rotary switch is provided for each set- 
ting. The rotary switch is adjusted using a small flatblade 
screwdriver. The selected setting for each adjustment will 

Digitrip RMS 

31 0 

Trip Units. Settings 

and 

are 

available on 2500A styles.  

4.3 Short Delay Time Settings 

For catalog numbers 

RESl 

and 

the short time delay is an 

ramp config- 

uration with the actual time delay a function if the trip cur- 
rent involved 

For catalog numbers 

and 

the short time delay is a flat response. 

Four settings 

(I, 

0.1, 0.2, 0.3 

second) are available (see 

Figure 

2.2). 

The 

setting gives a trip response with no 

intentional delay (Instantaneous). 

4.4 Instantaneous Pickup Setting 

For catalog numbers 

and 

Instantaneous Pickup is achieved by set- 

ting Short Delay Time to 

(Instantaneous.) Short Delay 

Pickup (see paragraph 

4.2) 

then becomes Instantaneous 

Pickup. 

4.5 Ground Fault Pick-up Setting 

Eight settings lettered A through 

K (there is no setting 

marked 

are available (see Figure 

2.3) 

and corre- 

spond to the fixed ampere values listed on the trip unit 

nameplate and in Table 

1.2. 

Note: These ampere values are always the same no 
matter what rating plug is installed in the circuit 
breaker. 

Available on Catalog 

Nos. 

RESl 

and 

4.6 Ground Fault Time Settings 

The ground fault time delay is a flat response with four 
settings 

0.15, 0.3, 

0.5 

second) available (Figure 

2-4). 

The 

I setting gives a trip response with no intentional 

delay (Instantaneous). This option is available on Catalog 

Nos. 

RESl 

and 

Effective 

February 2006

3.2 Overload Trip: 

In accordance with standards 

requirements, the trip unit initiates a trip of  the circuit 
breaker within two hours for an overload of  135 percent, 

and will trip in less time for higher overload currents. 

A “Thermal Memory” effect prevents the breaker from 

being re-energized immediately after an overload trip. A 
“cooling off” period of  up to 

minutes is required, which 

allows time for cabling to cool off. 

3.3 Short Delay/Instantaneous Trip:  For short circuit 

appear in a small rectangular window in the trip unit 
above the switch. 

4.2 Short Delay Pick-up Setting 

Seven settings are available that range from 

to 

(I,) as 

shown in Figure 

2.1. 

This feature is included on all 

CAUTION

LACK OF ILLUMINATION OF THE STATUS

LED DOES NOT INDICATE THE TERMINALS

OF THE BREAKER ARE DE-ENERGIZED

conditions that exceed the short delay pick-up settings,

the trip unit initiates a trip after a delay prescribed by the 

Page 3

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...S PRODUCTS The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment as well as all general and local health and safety laws codes and...

Page 2: ...eratures above 40 C with circuit breaker currents near full load For ambient conditions above 40 C and where the maxi mum ampere rating plug has been installed derating of the circuit breaker frame sh...

Page 3: ...e available see Figure 2 2 The 1 setting gives a trip responsewith no intentional delay Instantaneous 4 4 Instantaneous Pickup Setting For catalog numbers RES16OOLSI RES2000LS1 RES2500LS1 RES1600LSIG...

Page 4: ...Settings A B C D E F H K Specific Amperes Given in Table 1 2 Fig 2 3 GroundFault Pick Up Settings Short Delay Time r lSec Available Settings I l 2 3Seconds with Flat Response I I Fig 2 2 Short Delay...

Page 5: ...of the trip unit is set 2 The short delay pick up setting is a multiple of I 3 The ground pick up setting is independent of I Rating Plugs for the Digitrip RMS 310 Trip Units are marked for and may b...

Page 6: ...iiomat Fig 3 2 Trip Unit Nameplate Catalog Nos RES1600LS1 RESZOOOLSI and RES2500LSI ilrp RMS 310 1 Gnd Fig 3 3 Trip Unit Nameplate Catalog Nos RES1600LSG RESZOOOLSG and RES2500LSG Fig 3 4 Trip Unit Na...

Page 7: ...ating Plug Setting Amperes See Fig 2 6 a n d Fig 2 7 for Continuation of Short Time and Instantaneous Portions of Curves Current I Fig 5 1 OptionalAdjustable Ampere Setting Rating Plug Used in the Dig...

Page 8: ...Time 0with Adjustable Short Delay Pick up or Short Delay Digitrip RMS 310 Trip Unit Type Catalog Numbers RES1600LS RESl6OOLSI RES16OOLSG RESl600LSIG RES2000LS RES2000LSI RES2000LSG RES2000LSIG RES2500...

Page 9: ...able Trip Unit Ampere Rating Adjustable Rating Plugs 1600A 800A 1OOOA 1200A 1600A In 800A 1OOOA 1250A 1600AO In 2000A 1OOOA 1200A 1600A 2000A In 1000A 1250A 1600A 2000AO In 1200A 1600A 2000A 2500A In...

Page 10: ...NOTES Effective February 2006 I L 29C883E Page 10 Courtesy of NationalSwitchgear com...

Page 11: ...I L 29C883E NOTES EffectiveFebruary 2006 Page 11 Courtesy of NationalSwitchgear com...

Page 12: ...6 Printed USA TQC All Rights Reserved 2001 Eaton Corporation www eatonelectrical com tel 1 899 525 2000 USA Moon Township PA 15108 4312 1000 Cherrington Parkway Eaton Electrical business unit Eaton Co...

Reviews: