I.L. 29C883E

5.0 

TESTING 

A test receptacle is built into each trip unit to allow use of 
the STK2 Test Kit. The Test Kit performs a test of the 

Long Delay, Short Delay and Ground Fault functions. 

6.0 FRAME RATINGS AND RATING PLUGS 

The 

Frame Rating 

of  a circuit breaker is the maximum 

RMS current it can carry continuously. The maximum 
Short-circuit Current Ratings of the circuit breaker are 
usually related to the Frame Rating as well. 

It is often desirable to be able to choose a current value 

less than the full frame rating, to be the basis for the 

coordination of  the circuit breaker's protection functions, 
without affecting its short-circuit current capability. For the 

Digitrip 31 

Trip Unit this is implemented by changing the 

Rating Plug. 

For Adjustable Rating Plugs, Table 1-2, the primary cur- 
rent carrying conductors used with the breaker must be 

sized to correspond with the maximum setting of  the rat- 

ing plug, in accordance with National Electric Code 
req u 

i rements. 

The 

Rating Plug 

(See Fig. 5.2) fits into a special cavity to 

complete the trip unit. 

The 

Rating Plug 

current rating, 

is the basis for the 

trip unit current settings: 

1)  The long delay protection function of the trip unit is set 

2)  The short delay pick-up setting is a multiple of 

3)  The ground pick-up setting is independent of 

Rating Plugs for the Digitrip 

RMS 31 

Trip Units are 

marked for and may be applied on both 

50 

and 60 Hz 

Systems. 

at 

Complete catalog descriptions of  all available rating 
plugs are given in the applicable circuit breaker supple- 
mentary instruction leaflets (see Section 7.0). 

7.0 REFERENCES 

7.1 

Digitrip RMS Trip Assemblies 

I.L. 

I.L. 29-885 

I.L. 29-886 

I.L. 29-888 

7.2   R-Frame 

Molded Case Circuit Breakers 

29-1 07 

Frame Instruction Leaflet 

Supplementary Instructions for 

Instructions for  Digitrip 

RMS 31 

Trip Unit 

Instructions for  Digitrip 

RMS 510 Trip Unit 

Instructions for  Digitrip 

RMS 61 

Trip Unit 

Instructions for  Digitrip RMS 81 

Trip Unit 

R-Frame used with Digitrip 

RMS Trip 

Units 

Typical Time-Current Characteristic 

Curve for  R-Frame Circuit Breakers 

I.L. 

Master Connections Diagram for  
R-Frame Circuit Breaker with Digitrip 
RMS Trip Units 

DANGER 

BEFORE YOU FIT THE RATING PLUG INTO THE TRIP 

BE SURE TO CHECKTHAT THE BREAKER 

TYPE AND FRAME RATING, MATCH THOSE 

PRINTED ON THE RATING PLUG COVER. 

INSTALLING A RATING PLUG THAT DOES NOT 
MATCH THE BREAKER TYPE AND FRAME RATING, 
CAN PRODUCE SERIOUS 

AND/ 

OR 

FAILURE OF THE PROTECTION SYSTEM. 

Effective 

February 2006                                                                                                                                                                      

Page 5 

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...S PRODUCTS The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment as well as all general and local health and safety laws codes and...

Page 2: ...eratures above 40 C with circuit breaker currents near full load For ambient conditions above 40 C and where the maxi mum ampere rating plug has been installed derating of the circuit breaker frame sh...

Page 3: ...e available see Figure 2 2 The 1 setting gives a trip responsewith no intentional delay Instantaneous 4 4 Instantaneous Pickup Setting For catalog numbers RES16OOLSI RES2000LS1 RES2500LS1 RES1600LSIG...

Page 4: ...Settings A B C D E F H K Specific Amperes Given in Table 1 2 Fig 2 3 GroundFault Pick Up Settings Short Delay Time r lSec Available Settings I l 2 3Seconds with Flat Response I I Fig 2 2 Short Delay...

Page 5: ...of the trip unit is set 2 The short delay pick up setting is a multiple of I 3 The ground pick up setting is independent of I Rating Plugs for the Digitrip RMS 310 Trip Units are marked for and may b...

Page 6: ...iiomat Fig 3 2 Trip Unit Nameplate Catalog Nos RES1600LS1 RESZOOOLSI and RES2500LSI ilrp RMS 310 1 Gnd Fig 3 3 Trip Unit Nameplate Catalog Nos RES1600LSG RESZOOOLSG and RES2500LSG Fig 3 4 Trip Unit Na...

Page 7: ...ating Plug Setting Amperes See Fig 2 6 a n d Fig 2 7 for Continuation of Short Time and Instantaneous Portions of Curves Current I Fig 5 1 OptionalAdjustable Ampere Setting Rating Plug Used in the Dig...

Page 8: ...Time 0with Adjustable Short Delay Pick up or Short Delay Digitrip RMS 310 Trip Unit Type Catalog Numbers RES1600LS RESl6OOLSI RES16OOLSG RESl600LSIG RES2000LS RES2000LSI RES2000LSG RES2000LSIG RES2500...

Page 9: ...able Trip Unit Ampere Rating Adjustable Rating Plugs 1600A 800A 1OOOA 1200A 1600A In 800A 1OOOA 1250A 1600AO In 2000A 1OOOA 1200A 1600A 2000A In 1000A 1250A 1600A 2000AO In 1200A 1600A 2000A 2500A In...

Page 10: ...NOTES Effective February 2006 I L 29C883E Page 10 Courtesy of NationalSwitchgear com...

Page 11: ...I L 29C883E NOTES EffectiveFebruary 2006 Page 11 Courtesy of NationalSwitchgear com...

Page 12: ...6 Printed USA TQC All Rights Reserved 2001 Eaton Corporation www eatonelectrical com tel 1 899 525 2000 USA Moon Township PA 15108 4312 1000 Cherrington Parkway Eaton Electrical business unit Eaton Co...

Reviews: