Description
2.3 Basic unit
Air circuit breaker 3WL10
26
Manual, 11/2017, L1V30499596002-01
Breaking capacity
B
N
S
Rated ultimate short-circuit
breaking capacity AC
I
cu
415 / 440 V AC
kA
42
55
66
I
cu
500 / 525 V AC
kA
42
50
50
I
cu
690 V AC
kA
—
42
50
Rated service short-circuit
breaking capacity AC
I
cs
415 / 440 V AC
kA
42
50
50
I
cs
500 / 525 V AC
kA
42
50
50
I
cs
690 V AC
kA
—
42
50
Rated short-circuit making
capacity AC
I
cm
415 / 440 V AC
kA
88
121
145
I
cm
500 / 525 V AC
kA
88
105
105
I
cm
690 V AC
kA
—
88
105
Rated short-time withstand
current
I
cw
1 s
kA
42
42
50
I
cw
3 s
kA
24
24
36
Break time on opening
I < I
cw
ms
40
I > I
cw
ms
25
Rated conditional short-circuit
current of the non-automatic air
circuit breakers
I
cc
500 / 690 V AC
kA
—
42
50
Mechanical and electrical endurance with regular maintenance in accordance with the
manufacturer's instructions:
Mechanical endurance
I
u
≤ 1000
1250
Operating cycles
x 1000
20
20
Frequency Operating cycles/h
60
60
Electrical endurance
440 V
Operating cycles
x 1000
8
8
690 V
Operating cycles
x 1000
8
6.5
Operating cycles/h
30
30
Dimensions and weights:
Dimensions
Fixed breaker
H
mm
29
1
D
mm
183
W
3-pole
mm
210
4-pole
mm
280
Withdrawable
breaker
H
mm
363.5
D
mm
271
W
3-pole
mm
278
4-pole
mm
348
Weight
(with ETU and current sensor)
Fixed breaker
3-pole
kg
14
4-pole
kg
16
Withdrawable breaker
3-pole
kg
38
4-pole
kg
43
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......