Description
2.4 Electronic trip unit ETU
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
57
Protection functions of the ETU
ETU650 LSI
ETU660 LSIG
S
ST: Short-time-delayed short-circuit protection
Protection function can be enabled/disabled
●
●
Setting range of operating value I
sd
= I
n
x …
0.6 to 10 (in steps of 0.1)
Default value: OFF
Tolerance
1)
:
± 7% I ≤ 6 x I
n
± 10% I ≤ 6 x I
n
0.6 to 10 (in steps of 0.1)
Default value: OFF
Tolerance
1)
:
± 7% I ≤ 6 x I
n
± 10% I ≤ 6 x I
n
Short-circuit protection characteristic
Switchable
I²t / t = constant
Switchable
I²t / t = constant
Setting range for delay time t
sd
(fixed delay) t=k 0.05 to 0.4 s (in steps of
0.01)
Default value: 0.05
Tolerance
1)
: The better value
out of ± 10 % or ± 40ms
0.05 to 0.4 s (in steps of
0.01)
Default value: 0.05
Tolerance
1)
: The better value
out of ± 10 % or ± 40ms
Setting range for delay time t
sd
at I²t
(reference point 10 x I
n
)
0.05 to 0.5 s (inverse-time in
relation to I²t) (in steps of
0.01)
0.05 to 0.5 s (inverse-time in
relation to I²t) (in steps of
0.01)
Tripping can be deactivated
●
●
Switchover to alternative operating values with
short-time-delayed short-circuit current during
the switch-on phase (inrush adaptation) for
tripping characteristic t=k (fixed) possible
●
Default value: OFF
●
Default value: OFF
Setting range of the switch-on phase (inrush
adaptation)
0.1 to 30 s (in steps of 0.01)
Default value: 0.1
0.1 to 30 s (in steps of 0.01)
Default value: 0.1
Setting range Isd = In x … during the switch-on
phase (inrush adaptation)
0.6 to 10 (in steps of 0.1)
Default value: 10
0.6 to 10
(in steps of 0.1)
Default value: 10
I
INST: Instantaneous short-circuit protection I
i
Protection function can be enabled/disabled
●
●
Setting range for operating value I
i
= I
n
x …
1.5 to 15 (in steps of 0.1)
Default value: 2
Tolerance
1)
: ± 10%
1.5 to 15 (in steps of 0.1)
Default value: 2
Tolerance
1)
: ± 10%
Switchover to alternative operating values with
instantaneous short-circuit current during the
switch-on phase (inrush adaptation) for tripping
characteristic t=k (fixed) possible
●
Default value: OFF
●
Default value: OFF
Setting range of the switch-on phase
(inrush adaptation)
0.10 to 30 s (in steps of 0.01)
Default value: 0.1
Tolerance
1)
: ≤ 30 ms
0.10 to 30 s (in steps of 0.01)
Default value: 0.1
Tolerance
1)
: ≤ 30 ms
Setting range I
i
= I
n
x … during the switch-on
phase (inrush adaptation)
1.5 to 15 (in steps of 0.1)
Default value: 1.5
1.5 to 15 (in steps of 0.1)
Default value: 1.5
N
Neutral protection
Neutral protection can be enabled/disabled
●
●
Current setting value I
N
= I
n
x …
50 %; 100 %; 150 %; 200 % 50 %; 100 %; 150 %; 200 %
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......