Service and maintenance
7.5 Basic unit and accessories
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
175
7.5.4
Testing the ETU
Test with the TD310 Activation & Trip Box
1.
Connect the TD310 Activation & Trip Box to the ETU.
2.
Perform the trip test (see Chapter Application planning (Page 107) and Operating
Instructions).
3.
Check the correct cable connection to the tripping modules and to the release.
4.
For ETUs of the 6-series only: Call up the wear indicator on the contacts of the circuit
breaker on the display.
5.
After the work, remove the TD310 Activation & Trip Box from the ETU.
Check the TD410 Breaker Data Adapter and the TD420 test device.
1.
Connect the TD 410 or TD420 to the ETU and to a PC with the powerconfig software.
2.
Check whether there are any alarm messages and evaluate them (see Chapter Alarms
(Page 161)).
3.
If there are no alarm messages, perform the trip tests and self-tests with the test button
on the ETU or with the corresponding software functions of powerconfig.
4.
After the tests, remove the TD410 Breaker Data Adapter or TD420 test device from the
ETU and the PC.
Summary of Contents for SENTRON 3WL10
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Page 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Page 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Page 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Page 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Page 233: ......
Page 234: ......