Functions
Control sequences
4
A6V11545892_en--_a
63 | 150
The diagrams below show the control sequence for modulating PI control.
Heating mode
Cooling mode
T[°C] Room temperature
XpH Proportional band "Heating"
(P050)
w Room temperature setpoint
XpC Proportional band "Cooling"
| (P052)
YHC Control command "Valve" or
"Compressor"
XpR Proportional band "Radiator"
(P054)
YR Control command "Radiator"
X
dz
Dead zone (P055)
w
D
Setpoint differential (P056)
The diagrams only show the PI thermostat’s proportional part.
For setting sequence and control outputs, see Application overview [
Sequence overview (setting via P001) [
Parameter P256 (RDG260KN) sets the heating flow limitation when using a PICV.
Modulating control:
3-position, PWM or
DC 0...10 V
Note
Note