Functions
Operating modes
4
28 | 150
A6V11545892_en--_a
Function if no time schedule is received via bus
User profile for
operating mode
(selected via P002)
Operating
mode
when
activating
function
Mode
button
Function
Operating
mode during
function
Operating
mode at the
end of
function
P002 = 1:
Comfort
Extension Comfort
Protection
Comfort
Absence
Protection Comfort
P002 = 2:
Comfort
or
Economy
Extension Comfort
Economy
Comfort
or
Economy
Absence
Economy
Comfort
P002 = 3:
Comfort
Extension Comfort
Protection
hospitality
Comfort
Absence
Protection
hospitality
Comfort
Extension/absence is not available in Protection mode.
Function with time schedule via bus
User profile for
operating mode
(selected via P002)
Operating
mode when
activating
function
Mode
button
Function
Operating
mode
during
function
Operating
mode at
the end of
function
P002 = 1:
Auto
Extension Comfort
Auto
Comfort
Extension Comfort
Auto
Auto
Absence Protection Auto
Comfort
Absence Protection Auto
P002 = 2:
Auto,
Comfort or
Economy
Extension Comfort
Auto
Auto,
Comfort or
Economy
Absence Economy Auto
P002 = 3:
Auto
Extension Comfort
Auto
Comfort
Extension Comfort
Auto
Auto
Absence
Protection
hospitality
Auto
Comfort
Absence
Protection
hospitality
Auto
Extension/absence is not available in Protection mode.
Note
Note