Connection
Application examples
6
138 | 150
A6V11545892_en--_a
2-pipe and 2-stage application with radiant heating/cooling panels, the fan only
operates with the fan coil unit:
●
Heating sequence: 1
st
panel and 2
nd
fan coil unit
●
Cooling sequence: 1
st
fan coil unit and 2
nd
panel
Commissioning
Outputs used
●
Fan P350 = 6 (Cooling
and 2
nd
stage heating)
●
Valve P201 = 5 (panel)
●
Valve P203 = 5 (fan coil
unit)
●
Swap P254 = 1
●
M1 DC 0...10 V fan
(2
nd
stage)
●
V1 DC valve panel
●
V2 DC valve fan coil
unit
140] for min. and
max. ratings
RDG260KN
Example 2:
Swap and fan in the 2
nd
stage
Summary of Contents for RDG200KN
Page 146: ...Dimensions 8 146 150 A6V11545892_en _a 8 Dimensions Dimensions in mm ...