Connection
Application examples
6
136 | 150
A6V11545892_en--_a
Compressor application, with reversing valve (heating/cooling) and DC 0...10 V
fan:
Commissioning
Outputs used
●
Application 4-pipe
●
Control output P201 = 4 (On/Off)
●
Fan P351 = 3
(or DIP6 = OFF)
●
Relay function Heating/cooling
– ON in demand: P401 = 2
– Energized mode: Heating P401 = 5
– Energized mode: Cooling P401 = 6
●
M1 DC 0...10 V
fan
●
V1
*)
Reversing
valve
●
V2
*)
Compressor
●
K Relay
*)
Release contact
140] for min. and
max. ratings
RDG260KN
Example 3:
Compressor and
reversing valve