Functions
Control outputs
4
82 | 150
A6V11545892_en--_a
4.8.2 Control output configuration (setting via DIP switches 7/8 or
tool, and P201/P203/P204)
Application
Fan
Control outputs
Product
no.
DC 0...10 V 3-speed/
1-speed
Mod.
DC 0…10 V
On/Off
(2-pos)
On/Off
(3-wire)
Mod. PWM
(2-pos)
Mod.
3-pos.
RDG…KN
2-pipe
✓
✓
‒
✓
✓
✓
✓
200
✓
✓
✓
‒
‒
‒
‒
260
✓
‒
‒
✓
‒
‒
‒
260
2-pipe with
electric heater
✓
✓
‒
✓
✓
✓
✓
200
✓
✓
✓
‒
‒
‒
‒
260
✓
‒
✓
✓
‒
‒
‒
260
2-pipe with
radiator/floor
heating
✓
✓
‒
✓
✓
✓
✓
200
✓
✓
✓
‒
‒
‒
‒
260
✓
‒
✓
✓
‒
‒
‒
260
2-pipe/2-stage,
cooling or
heating
✓
✓
‒
✓
✓
✓
✓
200
✓
✓
✓
‒
‒
‒
‒
260
✓
‒
✓
✓
‒
‒
‒
260
4-pipe
✓
✓
‒
✓
✓
✓
✓
200
✓
✓
✓
‒
‒
‒
‒
260
✓
‒
✓
✓
‒
‒
‒
260
4-pipe with
electric heater
✓
✓
‒
✓
✓
✓
✓
1)
200
✓
✓
✓
‒
‒
‒
‒
260
✓
‒
✓
✓
2)
‒
‒
‒
260
Heating / Cooling
with 6-port valve
‒
‒
✓
‒
‒
‒
‒
260
Heating / Cooling
with 6-port valve
as changeover
and PICV valve
✓
‒
✓
✓
3)
‒
‒
‒
260
1)
Only available for cooling actuator
2)
Only selectable for electrical heater
3)
Relay outputs for 6-port valve as changeover
Note: On/off (2-pos) on RDG200.. are a triac outputs (max 1A), and relay outputs
(max 5(4)A) on RDG260..