Functions
Operating modes
4
A6V11545892_en--_a
31 | 150
Application for "Window contact", "Presence detector" and “Central time schedule”
In Room 3, the time schedule is between 13:00 and 17:00.
●
In the morning, as soon as presence is detected, the operating mode switches
to Comfort (1)
●
The users open the window briefly and the operating mode switches to
Protection (2)
●
In the afternoon, the central time schedule sets Comfort mode from 13:00 to
17:00 (3)
●
After 17:00, the room is still occupied, and the operating mode remains in
Comfort (occupancy via presence detector) (4)
●
The users open the window and exit the room for a short time. The operating
mode switches to Protection as long as the window is open (5)
●
As soon as the room is unoccupied, the thermostat switches to Economy (6)
●
After this time, occupancy detected by the presence detector has no effect, and
the central time schedule sets the thermostat to Protection (7)
Example 3