In 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone,
between the heating and cooling sequences.
The dead zone can be adjusted via P055.
If manual changeover is selected, either the cooling sequence or the heating
sequence is released. In this case, the Comfort setpoint is at the selected heating
or cooling sequence.
Application
Comfort mode
Economy/Protection mode
Heating and cooling
P010 = 1
Heating only
1)
or heating
and cooling
P010 = 1
Cooling only
1)
or heating
and cooling
P010 = 2
Heating and/or cooling
4-pipe
4-pipe with
electric heater
1)
Manual changeover, P001 = 3
W = Setpoint in Comfort mode
W
HeatEco/Prot
= Heating setpoint for Economy or Protection mode
W
CoolEco/Prot
= Cooling setpoint for Economy or Protection mode
YE = Electric heater sequence
4-pipe applications