d01
Application number
0 = (No application)
1 = 2-pipe
2 = 2-pipe with electric heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2-stage heating or cooling (2-pipe)
6 = 4-pipe with electric heater
7 = 2-stage heating and cooling (4-pipe)
8 = 4-pipe:6-port H/C (no fan)
9 = 4-pipe:6-port CO +PICV
‒
d02
X1 state
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00 = H/C Input shorted
100
= H/C Input open
‒
d03
X2 state
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00 = H/C Input shorted
100
= H/C Input open
‒
d04
U1 state
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
2 = Activated (DC input)
3 = Activated (DC output)
0…49 °C = Current temp. value (for AI)
00 = H/C Input shorted
100
= H/C Input open
‒
d05
1)
Test mode for checking the Y1/Y3 actuator's running
direction 5)
"---" = No signal on outputs Y1 and Y3
OPE = Output Y1 forced opening
CLO = Output Y3 forced closing
‒
d06
1)
Test mode for checking the Y2/Y4 actuator's running
direction 5)
"---" = No signal on outputs Y2 and Y4
OPE = Output Y2 forced opening
CLO = Output Y4 forced closing
‒
d08
Test mode for checking the Q1 output (ex P400
function)
"---" = no signal at output Q1
OPE = output Q1 forced opening
CLO = output Q1 forced closing
‒
d09
Test mode for checking the Q2 output (ex P401
function)
"---" = no signal at output Q2
OPE = output Q2 forced opening
CLO = output Q2 forced closing
‒
d10
Test mode for checking the Q3 output (ex P403
function)
"---" = no signal at output Q3
OPE = output Q3 forced opening
CLO = output Q3 forced closing
‒
d14
Software version
Ux.xx is displayed
‒
d15
Unit ID number (Serial number)
Unit ID is displayed (Serial number)
‒