Functions
Communication objects (S-Mode)
4
106 | 150
A6V11545892_en--_a
Obj
Object name
Function
Type/
length
Flags
Obj
Object name
Function
Type/
length
Flags
75
Hum. Control
mode
Inactive
Humidification
Dehumidification
20.115
1 byte
CRT
83
Enable or disable
Leaf indication
Enable
Disable
1.003
1 bit
CWU
Indicates the mode of the humidity control function:
0 = inactive
1 = humidification; relative humidity lower than setpoint low P026
2 = dehumidification; relative humidity higher than setpoint high
P024
3…255 = not used
Enables or disables the leaf (green or red) indication.
84
Keypad: Lock fan
speed
Lock
Unlock
1.002
1 bit
CWU
Locks or unlocks the fan operation keypad in current fan speed.
76
Enable electric
heater
Enable/disable
1.003
1bit
CWU
85
Keypad: Lock fan
speed in "auto"
mode
Lock
Unlock
1.002
1 bit
CWU
An electric heater can be disabled with this communication object
(e.g., to meet tariff regulations).
The same function is also available via local multifunctional input
X1/X2/U1 (P150, P153, P155).
Only one input source must be used, either local input X1/X2/U1or
KNX bus.
Locks or unlocks the fan operation keypad in “auto” speed.
86
Keypad: Lock the
setpoint shift
Lock
Unlock
1.002
1 bit
CWU
Locks or unlocks the setpoint shift keypad.
77
Built-in room
relative humidity
value [%r.h.]
I/O
9.007
2 bytes
CRT
87
Keypad: Lock the
operating mode
Lock
Unlock
1.002
1 bit
CWU
Locks or unlocks the operating mode keypad.
The value of the room humidity measured via built-in sensor is
available on bus.
78
External room
relative humidity
value [%r.h.]
I/O
9.007
2 bytes
CWU
The thermostat receives and works with the relative humidity value
from an external sensor.
79
Room rel.
humidity: Setpoint
high
I
9.007
2 bytes
CWU
Communication object adjusts the humidity setpoint high used by
the thermostat. It changes the value of P024.
S-Mode object must be enabled by setting "Humidity setpoints" to
"as group object" in ETS.
The humidity maximum setpoint is stored in EEPROM. The
service life of the EEPROM depends on the number of write
cycles. Never write this communication object cyclically.
80
Room rel.
humidity: Setpoint
low
I
9.007
2 bytes
CWU
Communication object adjusts the humidity setpoint low used by
the thermostat. It changes the value of P026.
S-Mode object must be enabled by setting “Humidity setpoints” to
“as group object” in ETS.
The humidity minimum setpoint is stored in EEPROM. The service
life of the EEPROM depends on the number of write cycles. Never
write this communication object cyclically.
81
Reset the Energy
efficiency status
(Green leaf)
No action
Reset
1.017
1 bit
CWU
Resets the settings to green leaf.
82
Energy efficiency
status / Green Leaf
Green
Red
1.006
1 bit
CRT
Indicates current status of green leaf.