Functions
Control parameters
4
116 | 150
A6V11545892_en--_a
Para
meter
Name
Fa
cto
ry
s
et
ting
Ran
ge
RDG2
00
KN
RDG2
60
KN
Dep
en
den
cie
s
Expert level
P365
Fan start delay
0 s
0...360 s
✓
✓
P350
P366
Fan start, minimum hot water
temperature
30 °C
OFF,5…60 °C
✓
✓
P350
Input
Relay functions
P400
9)
Output Q1 function
0
0 = No function
1 = Switch OFF in Protection
2 = Switch ON in Heat/Cool demand
3 = Switch ON in Heat demand
4 = Switch ON in Cool demand
5 = Heating sequence active
6 = Cooling sequence active
7 = External dehumidifier control
8 = External humidifier control
✓
✓
P350,
P351
P401
9)
Output Q2 function
P402
Output Q3 function
Controller
P450
Control strategy
0
0 = Temperature (T)
1 = Temperature (T) + Relative humidity
(r.h.)
✓
✓
‒
P451
Humidity control strategy
2
1 = With setpoint shift
2 = With setpoint shift + external
equipment (humid / dehum)
✓
✓
‒
P461
T setpoint shift (humidity)
3 K
-3…3 K
✓
✓
‒
Side Features
P500
NFC
ON
ON = Enabled
OFF = Disabled
✓
✓
‒
P501
Service filter
OFF
OFF, 100…9900 h
✓
✓
P350
P502
Password
OFF
ON = Enabled
OFF = Disabled
✓
✓
‒
P503
Password
000
000…999
✓
✓
‒
P505
Restore factory setting
OFF
OFF = Disabled
ON = Reload start
✓
✓
‒
System
P900
Device address 3)
255
1…255
✓
✓
‒
P901
Geographical zone (apartment) 4)
---
---(0), 1...126
✓
✓
‒
P902
Geographical zone (room) 3)
1
---(0), 1...63
✓
✓
‒
P903
Heat distr zone heating coil
---
---(0), 1...31
✓
✓
‒
P904
Refrig distr zone cooling coil
P905
Heat distr zone heating surface
P910
Transformation Precomfort
0
0 = Economy
1 = Comfort
✓
✓
‒
Note: Parameter display depends on selected application and function. Appl
means application.
1)
When P201/P203 = 1/3/5, P204 = 3/5, P057 & P058 are visible.
2)
When P150, P153 or P155 = 2 and P001 = 2, P059 & P060 are visible.
3)
When P002
≠
2, P102 is visible.
4)
Only available for application 2-pipe/2-stage.
5)
When P201 = 3, P206 is visible; P203 = 3, P207 is visible; P204 = 3, P208 is
visible.
6)
When P201 = 1, P214 is visible; P203 = 1, P215 is visible.
7)
When “H/C changeover” function on X1, X2, U1 is selected, P251 is visible.
8)
When “External temperature limit (AI)” on X1, X2, U1 is selected, P252 is visible.
9)
When application is 4-pipe with 6-port ball valve as changeover and PICV, P400
& P401 are invisible.