4.6 Additional functions
Functions (parameters)
Description
RDG260KN
RDG200KN
Sensors and changeover functions [
●
Heating/cooling changeover via bus (KNX) Central control of heating / cooling via bus
✓
✓
●
Automatic heating/cooling changeover via
changeover sensor
●
Changeover switch (P150, P153, P155)
Thermostat runs sequences depending on the
water temperature
✓
✓
✓
✓
●
Manual heating/cooling changeover
(P001)
Heating / cooling controlled manually by user
(via HMI)
✓
✓
●
External/return air temperature sensor
(P150, P153, P155)
Temperature measurement using external
sensors
✓
✓
●
Standard presence mode (P150 / P153 /
P155)
Switch operating mode locally or via bus
✓
✓
●
Hotel presence mode (P150 / P153 /
P155)
Switch operating mode locally or via bus
✓
✓
●
Purge function (P251)
To ensure correct acquisition of the water
temperature
✓
✓
●
Minimum output On/Off time (P212, P213) To protect HVAC equipment, e.g., compressor
and reduce wear and tear
✓
✓
●
Swap outputs for 2-pipe and 2-stage
applications (P254)
To optimize use of heating/cooling energy in
mixed systems
✓
✓
●
Floor heating/cooling (P350)
Application without fan control
✓
✓
●
Qx relay switching function (P400, P401,
P402)
Control external equipment based on function
state (heating/cooling demand, operating mode,
sequence, humidity, …)
✓
✓
Monitoring and limitation functions [
●
Floor temperature limitation function
(P252)
For user Comfort and floor protection
✓
✓
●
Supply air temperature limitation (P063,
P064)
To save energy, by avoiding room air that is too
hot or cold
✓
✓
●
Flow limitation in heating for PICV (P256) To balance heating and cooling and avoid
hydraulic issues due to different flow rates
✓
✓
●
Dewpoint monitoring
●
Fault state “condensation” (P150, P153,
P155 = 4)
To prevent condensation damage in the building
✓
✓
✓
✓
●
Valve exercising (P250)
To prevent valve freezing after extended
inactivity
✓
✓
●
Button lock (P028)
To limit access by unauthorized persons
✓
✓
●
Green leaf (P110, P111)
Indication on energy efficiency
✓
✓
●
Humidity control (P007, P450)
Limit min. and max. humidity in the room
✓
✓
●
Avoid cold air in heating mode (P365)
To ensure setpoint temperature is reached
during heating
✓
✓
●
Avoid damage from moisture (P363, P364) To prevent damages caused by moisture
✓
✓
●
NFC (P500)
NFC communication via Siemens smartphone
application
✓
✓