4.7 Control sequences
4.7.1 Sequence overview (setting via P001)
The main control sequence (water coil sequence of the fan coil unit) can be set via
P001.
The following sequences can be activated in the thermostats (with or without
auxiliary heating).
The available sequences depend on the application (selected via DIP switches,
37]).
Parameter
P001 = 0
P001 = 1
P001 = 2
P001 = 3
P001 = 4
Sequence
Available for basic
application 1):
⇓
Heating
Cooling
= Heating sequence
for electric
heater/radiator
Automatic
heating/cooling
changeover via
external water
temperature sensor or
remote switch
Manually select
heating or cooling
sequence (using HMI)
Heating and cooling
sequence , 4-pipe
2-pipe
2-pipe with el. heater
2-pipe with radiator
4-pipe
4-pipe with el. heater
2)
2-pipe/2-stage
heating or cooling
1)
For chilled/heated ceiling and radiator applications, see Chilled/heated ceiling
2)
For manual changeover with 4-pipe applications, see 4-pipe fan coil unit [
●
4-pipe manual changeover (P001 = 3) means activating either cooling or
heating outputs
●
P001 cannot be configured for applications with 6-port ball valve.
For the relationship between setpoints and sequences, see Setpoints and