Functions
Control sequences
4
A6V11545892_en--_a
71 | 150
4.7.9 Chilled/heated ceiling and radiator applications
For chilled/heated ceiling and radiator applications
●
Set the corresponding basic application see Application overview [
●
Disable the fan (P350)
The following applications are available:
Application for
chilled/heated
ceiling, radiator
Basic application
Section
Sequences
Chilled/heated
ceiling with
changeover
2-pipe
H ( \ )
C ( / )
Chilled/heated
ceiling and electric
heater (cooling
only: disable
electric heater via
P027)
2-pipe with electric
heater
El H + H (
↯
\ \ )
El H + C (
↯
\ / )
C ( / )
Chilled/heated
ceiling and radiator
2-pipe with radiator 2-pipe fan coil unit
H + rad ( \ r\ )
Rad + C ( r\ / )
Chilled ceiling and
radiator
4-pipe
H + C ( \ / )
Chilled/heated
ceiling, 2-pipe/2-
stage
2-pipe/2-stage
heating or cooling
H + H ( \ \ )
C + C ( / / )
Summary of Contents for RDG200KN
Page 146: ...Dimensions 8 146 150 A6V11545892_en _a 8 Dimensions Dimensions in mm ...