802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
47/293
Description
Cellpack
50…240
25…240
EPDM 1x CTS 630A 24kV
2x CTKS 630A 24kV
3x distribution kit
-
IEC
1x CTS 630A 24kV*
2x CTKS 630A 24kV*
3x distribution kit*
-
IEC
1
At a continuous current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required.
2
Observe the actual current- and short-circuit-carrying capacity of the cables and sealing ends.
Circuit-breaker panel 630 A, 1000 A ● Switch-disconnector panel 630 A ● Disconnector panel 1000 A ● Ring-main panel 630 A ● Vacuum
contactor panel ● Circuit-breaker panel with top-rear cable connection 1250 A
1
Panel spacing 600 mm
Make
Conductor
cross-
section
2
In
su
la
ti
on
Cable T-plugs
Coupling inserts/
coupling plugs
Distribution kit for
three-core cables
Surge arresters
According to
standard
[mm
2
]
bolted
bolted
additionally
• GOST (Russia,
CIS)
• GB/DL (China)
12 kV
24 kV*
12 kV
24 kV*