802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
275/293
Service information
29
Checks and maintenance work in case of special
operating conditions
If the switchgear is used in abnormally unfavorable indoor conditions beyond the normal
operating conditions (e.g. frequent heavy condensation, dust-ridden air, etc.) it is
recommended to perform a visual inspection of the NXPLUS C switchgear at regular intervals.
DANGER
Hazardous voltage.
Will cause death, serious injury and property damage.
Always observe the Five Safety Rules:
➭ Isolate.
➭ Secure against reclosing.
➭ Verify safe isolation from supply.
➭ Earth and short-circuit.
➭ Cover or barrier adjacent live parts.
DANGER
Life-endangering voltage
Can cause death, injury or property damage. If the operating mechanism cover is
removed, do not touch any live parts.
➭ Switch off auxiliary voltage.
WARNING
High speed moving parts
Can cause serious injury.
Do not remove the front cover of the operating mechanism until the following actions have
been performed:
➭ To avoid impermissible switching operations, switch off auxiliary voltage, e.g.:
- Switch the auxiliary voltage supply of the motor.
- Trip the MCB.
- Disconnect the control cables from the low-voltage compartment.
➭ To discharge the spring energy store in the operating mechanism, execute the following
instructions:
- Actuate the manual OFF pushbutton.
- Actuate the manual ON pushbutton.
- Actuate the manual OFF pushbutton again.
➭ Check if the "spring charged" indicator shows "spring charged".