32.4
Technical data
Binary inputs
Command input, feedback and interlocking is done through a total of 9 binary inputs (BI).
32.5
Fault signals
Output of fault signals
Fault signals at the unit are displayed via a red flashing LED status indicator.
Possible causes for a fault signal:
• An incorrect sense of rotation of the motor was detected while moving the operating
mechanism from disconnector OPEN / earthing switch OPEN position to
disconnector CLOSED / earthing switch CLOSED position.
• There is an internal MCU-MH fault (watchdog).
• The feedback monitoring time (runtime monitoring of the operating mechanism) for
protecting the drive motor and the mechanical system was exceeded.
• A command for moving the operating mechanism is applied to the active command inputs
(disconnector CLOSED / disconnector OPEN / earthing switch CLOSED / earthing
switch OPEN) for more than 5 minutes, although existing interlocking conditions prevent
the execution of this command.
Binary input
Description
Type
Electrical function
Function
1
Command inputs
Active
High active
Disconnector in CLOSED position
1
2
Disconnector in OPEN
1
position
3
Earthing switch in CLOSED
1
position
4
Earthing switch in OPEN
1
position
5
Interlocking inputs
Passive
High active
Total of all interlocking conditions, release of control
unit with applied high signal
6
Passive
Low active
Other interlock / 2-phase switching of the disconnector
and earthing switch function
7
Feedback inputs
Passive
High active
Disconnector and earthing switch in OPEN
1
position
8
Disconnector in CLOSED
1
position
9
Earthing switch in CLOSED
1
position
1
Depending on the panel type and the necessary sense of rotation of the motor, the assignment of the sense of rotation of the motor can
vary.
NOTICE
Functional failure due to insufficient voltage quality
The functioning of MCU-MH may be impaired.
➭ The voltage quality of the voltages used for auxiliary and load circuits must correspond to
applicable standards.
➭ If an AC control or AC load voltage is used, which is generated directly from single-phase
inverters, earth U
N2~
.
NOTICE
Functional failure due to incorrect circuit of the command inputs
The functioning of MCU-MH may be impaired.
➭ For activation of the command inputs for disconnector CLOSED, disconnector OPEN,
earthing switch OPEN and earthing switch CLOSED, do not use any external switching
contacts that are equipped with capacitors > 4.7 nF connected in parallel with the contact.
NOTICE
Damage to MCU-MH due to test voltages
If the specified limits (1 kV, 1 s) are exceeded during dielectric tests according to the
standard IEC 62271-200, the MCU-MH may be damaged by too high test voltages.
➭ Before performing the dielectric test, remove the connecting plugs at the MCU-MH.