802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
147/293
Installation
Component tables 1 and 2: Examples for busbar covers (view from the rear)
Installation for
component tables 1 and 2
➭
Panel without pressure relief
: Bolt supporting angles ① together with the rear walls.
Fig. 103: Mounting the supporting angles (view from above, example)
➭ Bolt the cover ② together with the panel.
➭
The panel is an end panel:
Fasten the termination angle ③ .
➭
Panel version 31.5 kA:
Bolt the reinforcing plate ④ together with the covers.
➭ Mount the left-hand ⑤ or right-hand sealing angle ⑥ under the following preconditions:
- The panel has a width of 900 mm and is in free-standing arrrangement.
- The adjacent panel has a width of 600 mm.
➭ Repeat the installation of the busbar cover for all panels.
✔ The installation of the busbar cover is completed.