Description
72/293
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
10.7
Rating plates
IAC classification
The data ④ describes the internal arc classification of the panel according to IEC 62271-200.
The data describes the areas classified for the corresponding panel (see page 59,
"Classification of NXPLUS C according to IEC 62271-200").
10.8
Vacuum circuit-breaker
Operating cycles 3AH55
Fig. 38:
Permissible number of operating cycles n as a function of the breaking current I
a
(r.m.s. value) in kA
Fig. 36:
Rating plate on the inside of the low-
voltage compartment
Fig. 37:
Rating plate at the switchgear
vessel
①
Switchgear type
⑤
Number of operating cycles
②
Serial number
⑥
Year of manufacture
③
Panel number
⑦
Technical data
④
Internal arc classification
Rated voltage
kV
7.2
12
15
17.5
24
Rated current
A
≥ 1000/1250/2000/2500
≥ 1000/1250/2000
Rated short-time withstand
current
kA
31.5
25
Rated normal current
Operating
cycles
10000
Short-circuit breaking current
Operating
cycles
50