Operation
Vacuum contactor panel: De-earthing the feeder
1
Initial situation
2
➭ Push the interrogation lever downwards and
hold it.
3
➭ Push the control gate to the right (the
interrogation lever locks in lower position.
The actuating opening for the EARTHING
function opens).
4
➭ Switch the three-position switch-
disconnector from EARTHED to OPEN
position (insert the operating lever and turn
90° counter-clockwise).
5
➭ Remove the operating lever (the
interrogation lever and the control gate
return to their initial position. The actuating
opening closes).