802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
265/293
Operation
16
➭ To de-earth the feeder, open the circuit-
breaker.
17
➭ Push the interrogation lever downwards
again and hold it.
18
➭ Push the left-hand control gate to the right
and hold it (the interrogation lever locks in
lower position. The left-hand actuating
opening for the READY-TO-EARTH function
opens).
19
➭ Switch the left-hand three-position
disconnector from READY-TO-EARTH to OPEN
position (insert the operating lever and turn
90° counter-clockwise).
20
➭ Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).