Communications
11.5 Modbus RTU/ASCII Protocol
BW500 and BW500/L
140
Operating Instructions, 12/2016, A5E33482052-AD
Format Register:
Bits
Values
Description
1 - 8
0 - 2
Error Code
9 - 11
0 - 7
decimal offset
12
0/1
decimal shift, Right (0) or Left
(1)
13
0/1
Numeric format: Fixed (0) or
FLoat (1)
14
0/1
Read or Write of data, Read (0),
Write (1)
15
0/1
Word order: Most Significant
word first (0), Least Significant
Word first (1)
16
Reserved
The bits listed above are in order from least to most significant:
16 15 14 13 12
11
10
9
8
7
6
5
4
3
2
1
For example, to format the output value so that it is shown with two decimal places shifted to the
left the format bits would look like this:
16 0
reserved
15 0
most significant first
14 0
read
13 1
float format
12 0
decimal 2
11 0
10 1
9
0
8
0
no error code
7
0
6
0
5
0
4
0
3
0
2
0
1
0
The value sent to the BW500 and BW500/L is 0001001000000000 binary or 4608 decimal.
The value 4608 is sent as an integer to register 40,093 to format the output words 40,094 and
40,095 accordingly.
Summary of Contents for Milltronics BW500
Page 1: ...Operating Instructions Milltronics BW500 and BW500 L 12 2016 Edition Integrators ...
Page 12: ...Table of contents BW500 and BW500 L 10 Operating Instructions 12 2016 A5E33482052 AD ...
Page 14: ...Safety Notes BW500 and BW500 L 12 Operating Instructions 12 2016 A5E33482052 AD ...
Page 16: ...The Manual BW500 and BW500 L 14 Operating Instructions 12 2016 A5E33482052 AD ...
Page 48: ......
Page 154: ......
Page 218: ...Index BW500 and BW500 L 216 Operating Instructions 12 2016 A5E33482052 AD ...
Page 219: ......