
65/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
5 Fuel / air ratio control (FARC)
13.08.2004
If, due to external effects, an actuator moves from its required position by more than
± 0.3° (neutral band) for more than 8 seconds, the supply of fuel will be shut down.
t
Pos. [°]
Required
position
-0,3
0,3
-2
2
0
< 5 s
755
0d15E
/0502
t
-0,3
0,3
-2
2
0
Alarm
< 5 s
Pos. [°]
Required
position
Successful correction < 2°
Fault < 2° (Stall point at constant output)
The required position is considered to be reached when it is within
±
0.3°.
When reaching a new position within
±
0.3°, the fuel / air ratio control system makes a
fine adjustment on the actuators.
Readjustments of the position are made only if the current position deviates from the
required position by more than 0.3°, followed by another fine adjustment.
If, during the load change, an actuator is mechanically blocked, the supply of fuel will
be shut down within 3 or 8 seconds.
7550d18E/0502
t
Pos. [°]
< 5 s
-0,3
0,3
-2
Alarm
Actual
position
Required
position
Locking on change of load (approach < 2° > 0.3°)