Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Description
Value range
Access
rights
Default pa-
rameter
setting
LMV51 LMV52
141/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
7 Display and operating unit AZL5...
13.08.2004
Modbus
User x
x
Address
Modbus address of LMV5...
1..247
User
1
x
x
Baudrate
Modbus rate of transmission
19200 bit/s
9600 bit/s
User
19200 bit/s
x
x
Parity
Modbus parity for LMV5...
no
even
odd
User
no
x
x
Timeout
Maximum time with no communication. When this period of
time has elapsed, "Remote" changes to "Local"
0..7200 s
User
30 s
x
x
Lokal / Remote
Change of operating mode local / remote
local
remote
User
---
x
x
Remote Mode
Operating mode: Remote "off" / remote "on" / W3
Automatic
Burner on
Burner off
User
---
x
x
W3
External setpoint W3, in °C
External setpoint W3, in bar
0..2000 °C
0..100 bar
User
---
x
x
Display Contrast
User x
x
ProductID
Displaying the HW version of the AZL5...
User x
x
ASN
Type reference
1..15 characters
User
"AZL52.00A
1WH"
x
x
ProductionDate
Production date
01.01.00..31.12.99
01-01-00..12-31-99
User
---
x
x
SerialNumber
Serial number
0..65535
User
---
x
x
ParamSet Code
Preselected parameter set: customer code
0..255
User
20
x
x
ParamSet Vers
Preselected parameter set: version
0..65535
User
430
x
x
SW Version
SW version of AZL5...
0..65535
User
---
x
x
Actuators
Settings for the actuators
User x
x
Addressing
Addressing unaddressed actuators
Service x
x
1 AirActuator
Actuator to be addressed becomes the air actuator
Service x
x
2 GasActuat(Oil)
Actuator to be addressed becomes the gas actuator, or the
fuel actuator for dual fuel burners with one fuel actuator
Service x
x
3 OilActuator
Actuator to be addressed becomes the oil actuator
Service x
x
4 AuxActuator
Actuator to be addressed becomes the auxiliary actuator
Service x
x
5 AuxActuator2
Actuator to be addressed becomes the auxiliary actuator
Service
x
6 AuxActuator3
Actuator to be addressed becomes the auxiliary actuator
Service
x
DirectionRot
Service x
x