239/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A6
EC
LC
Internal Fault Load Controller
Invalid branch in eeprom module()
*1)
A6
ED
LC
Internal Fault Load Controller
Invalid branch in eeprom module()
*1)
A6
EE
LC
Internal Fault Load Controller
Invalid branch in eeprom module()
*1)
A6
EF
LC
Internal Fault Load Controller
Invalid branch in eeprom module()
*1)
A6
F0
LC
Internal Fault Load Controller
Fault during ROM test
*1)
A6
F1
LC
Internal Fault Load Controller
Fault during RAM test
*1)
A6
F2
LC
Internal Fault Load Controller
Fault during RAM test, register bank 0
*1)
A6
F3
LC
Internal Fault Load Controller
Fault during RAM test, IDATA range
*1)
A6
F4
LC
Internal Fault Load Controller
Fault during RAM test, XDATA range
*1)
A6
F5
LC
Internal Fault Load Controller
Stack pointer does not point at stack
*1)
A6
F6
LC
Internal Fault Load Controller
Stack overflow
*1)
A6
FE
LC
Internal Fault Load Controller
Fault messages in fault management
*1)
A6
FF
LC
Internal Fault Load Controller
Fault messages in fault management
*1)
A7
#
AZL
AZL5…has detected own fault and re-
ported it to the basic unit.
Type of fault: See diagnostic code
Check CAN cabling and terminators as specified
Observe instructions given below, and:
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective AZL…
A7
01
AZL
Internal Fault AZL
CRC fault during ROM test
A7
02
AZL
Internal Fault AZL
CRC fault during RAM test
A7
04
AZL
Internal Fault AZL
Fault during key value check
A7
05
AZL
Internal Fault AZL
Time block overflow
A7
07
AZL
Internal Fault AZL
Sync fault or CRC fault
A7
08
AZL
Internal Fault AZL
Fault main loop counter
A7
09
AZL
Manual Lockout AZL
Fault message for emergency off function
via AZL…
A7
0A
AZL
Internal Fault AZL
Invalid AZL5… page
A7
0B
AZL
>250,000 startups, service required
A7
0C
AZL
Internal Fault AZL
Save fault parameter