Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Description
Value range
Access
rights
Default pa-
rameter
setting
LMV51 LMV52
126/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
7 Display and operating unit AZL5...
13.08.2004
Configuration
USER x
x
ConfigGeneral
General parameters of burner control
Service x
x
AlarmStartPrev
With / without alarm in the event of start prevention and heat
demand
deactivated
activated
Service deactivated
x
x
NormDirectStart
Normal / direct start in the event of heat demand in phase 78
NormalStart
DirectStart
OEM
NormalStart
x
x
OilPumpCou-
pling
Configuration for coupling the oil pump
Magnetcoupl
Directcoupl
OEM
Magnet-
coupl
x
x
IgnOilPumpStart
Switch-on time of ignition and oil pump
on in Ph38
on in Ph22
OEM
on in Ph38
x
x
ForcedIntermit
With / without forced intermittent operation
deactivated
activated
Service
activated
x
x
Continu-
ousPurge
Configuration for normal or continuous fan operation
deactivated
activated
OEM
deactivated
x
x
FuelTrainGas
Fuel train when firing on gas
DirectIgniG
Pilot Gp1
Pilot Gp2
OEM
invalid
x
x
FuelTrainOil
Fuel train when firing on oil
LightOilLO
HeavyOilHO
LO w Gasp
HO w Gasp
OEM
invalid
x
x
FuelTrainReset
Resetting the fuel train to invalid value
OEM x
x
FuelTrainGas
OEM x
x
FuelTrainOil
OEM x
x
ContPilotGas
Continuous pilot gas
deactivated
activated
OEM
deactivated
x
ContPilotOil
Continuous pilot oil
deactivated
activated
OEM
deactivated
x
MainsFrequency
Selection of mains frequency 50 / 60 Hz
50 Hz
60 Hz
OEM
50 Hz
x
x
ConfigIn/Output
Configuring the inputs and outputs
OEM x
x
StartReleaseGas
Input start release gas active
deactivated
StartRelGas
CPI Gas
CPI Gas + Oil
CPI Oil
OEM
StartRelGas
x