233/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A6
17
LC
Cold Start thermal Shock Protec-
tion active
*1)
A6
18
LC
Timeout with Adaption
Timeout during delivery of adaption rate
and while process is being watched
*1)
A6
22
LC
Setpoint Temp Controller above
maximum Limit
*1)
A6
30
LC
Internal Fault Load Controller
EEPROM does not respond within the
expected period of time
*1)
A6 31 LC
Internal Fault Load Controller
Max. number of EEPROM attempts ex-
ceeded
*1)
A6
32
LC
Internal Fault Load Controller
Fault during opening of page
*1)
A6
33
LC
Parameter Set damaged
Invalid CRC when reading a page
Reset the unit, repeat backup restore if necessary
A6
34
LC
Internal Fault Load Controller
Page cannot be set to FINISH
*1)
A6
35
LC
Internal Fault Load Controller
No access to PID after identification
*1)
A6
36
LC
Internal Fault Load Controller
No access to PIDStandard after identifi-
cation
*1)
A6
37
LC
Internal Fault Load Controller
No reading of EEPROM write access for
PID possible
*1)
A6
38
LC
Internal Fault Load Controller
No EEPROM write access for PID possi-
ble
*1)
A6
39
LC
Internal Fault Load Controller
No EEPROM write access for PIDStan-
dard possible
*1)
A6
3A
LC
Internal Fault Load Controller
No access if reception via COM
*1)
A6
3B
LC
Internal Fault Load Controller
Invalid page access
*1)
A6
40
LC
Internal Fault Load Controller
Page too long open
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL… pa-
rameters.
Otherwise, replace defective basic unit