16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
46
02
BU
Programstop active
Program stop "STOP_PREP2" in Phase
32 active
46
03
BU
Programstop active
Program stop "STOP_DR_IGN" in Phase
36 active
46
04
BU
Programstop active
Program stop "STOP_INTERV1" in
Phase 44 active
46
05
BU
Programstop active
Program stop "STOP_INTERV2" in
Phase 52 active
46
06
BU
Programstop active
Program stop "STOP_DR_POSTP" in
Phase 72 active
46
07
BU
Programstop active
Program stop "STOP_PREP2" in Phase
76 active
47
---
BU
No Start Release for Gas
Start release gas = off
48
---
BU
2 Flame Signals with 1 Detector
Operation
System parameterized for 1-detector op-
eration but 2 flame signals present
50
#
BU
Internal Fault Basic Unit
Fault during key value check
*1)
50
00..07
BU
Internal Fault Basic Unit
Number of time block in which the fault
was detected
51
#
BU
Internal Fault Basic Unit
Time block overflow
*1)
51
00..07
BU
Internal Fault Basic Unit
Number of time block in which the fault
was detected
52
#
BU
Internal Fault Basic Unit
Stack error
*1)
52
01
BU
Internal Fault Basic Unit
Stack overflow
52
02
BU
Internal Fault Basic Unit
Value dropped below preset minimum
limit
52
03
BU
Internal Fault Basic Unit
Test values in stack range exceeded
53
01
BU
Internal Fault Basic Unit
Faulty reset state has occurred
*1)