
209/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
15
01
SA
Fault Positioning Actuator
Positioning fault air actuator
15
02
SA
Fault Positioning Actuator
Positioning fault fuel actuator
15
04
SA
Fault Positioning Actuator
Positioning fault auxiliary actuator 1
15
08
SA
Fault Positioning Actuator
Positioning fault auxiliary actuator 2
15 10
VSD
module Fan Speed not reached
The fan in combination with the VSD has
not reached the required speed
Check characteristics of VSD for linearity. Remove filters,
damping and delay members
15
20
SA
Fault Positioning Actuator
Positioning fault auxiliary actuator 3
16
#
BU
Internal Fault Basic Unit
Basic unit has detected a plausibility fault
in the ratio control system.
The diagnostic code describes the cause
of the fault.
16
00
BU
Internal Fault Basic Unit
Ratio curve of the air actuator is not fully
defined
Check the curve to see if correct values have been entered
for the air actuator. Readjust the ratio curve, if required
16
01
BU
Internal Fault Basic Unit
Ratio curve of the fuel actuator is not fully
defined
Check the curve to see if correct values have been entered
for the fuel actuator. Readjust the ratio curve, if required
16
02
BU
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 1 is not
fully defined
Check the curve to see if correct values have been entered
for auxiliary actuator 1. Readjust the ratio curve, if required
16
03
BU
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 2 is not
fully defined
Check the curve to see if correct values have been entered
for auxiliary actuator 2. Readjust the ratio curve, if required
16
04
BU
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 3 is not
fullydefined
Check the curve to see if correct values have been entered
for auxiliary actuator 3. Readjust the ratio curve, if required